EU STOCK CATL 314AH, 6000 times life (on the way, middle of March. arrive)
EU STOCK CATL 314AH, 6000 times life (on the way, middle of March. arrive)
Couldn't load pickup availability
EU STOCK CATL 314AH,lifepo4 (on the way, middle of March. arrive)
Standard capacity | 314ah |
Operating Voltage | 2.5~3.65V 2.0~3.65V |
Battery internal resistance (1KHz) |
0.18±0.05m Ω |
Shipping capacity | 117~123Ah--40% SOC |
Monthly self- discharge |
≤3.5% |
Working temperature (charging) |
0~60℃ |
Working temperature (discharge) |
-30~60℃ |
Battery weight | 5.51KG |
Cell cycle | ≥8000cycles |
Standard charging current |
0.5C |
Maximum continuous charging current |
1C |
Standard charging temperature |
25±2 ℃ |
Application conditions
Customers should ensure that the following battery-related application conditions are strictly adhered to:
4.1 The customer should configure a battery management system to closely monitor, manage and protect each battery.
4.2 The customer shall provide CATL with detailed design plan, system features, framework, system data, format and other related information ofthe battery management system for CATL
to evaluate the system design and establish battery management files
4.3 Without the consent of CATL, customers are not allowed to modify or change the design and framework of the battery management system, so as not to affect the performance of the
battery.
4.4 The customer shall keep complete monitoring data ofbattery operation as a reference for the division ofproduct quality responsibilities. Ifthere is no complete battery system
monitoring data within the service life, CATL does not assume the responsibility of product quality assurance.
4.5 The battery management system needs to meet the following most basic testing and control requirements.
Share